Enhance your industrial control system's precision and reliability with the Delta DVP04TC-E2 4 Point Thermocouple Module. Designed to seamlessly integrate into your automation setup, this module offers advanced functionalities for temperature measurement across multiple thermocouple types - K, J, R, S, T, E, and N.
1. Multipoint Temperature Monitoring: With four input channels, this module enables simultaneous monitoring of multiple temperature points, enhancing operational efficiency and control.
2. Wide Thermocouple Compatibility: Supports a broad range of thermocouple types (K, J, R, S, T, E, N), providing versatility for various industrial applications.
3. High Accuracy and Precision: Industry-leading accuracy ensures precise temperature measurements, crucial for maintaining optimal operational conditions.
4. Enhanced Isolation for Reliability: Robust channel-to-channel and channel-to-ground isolation prevent interference, ensuring reliable and accurate data acquisition.
5. Seamless Integration: Compatible with Delta's DVP series PLCs, facilitating easy integration into existing control systems without extensive reconfiguration.
6. Compact and Efficient Design: Its compact form factor allows for space-saving installation, ideal for applications with limited space availability.
7. Robust Communication Interface: High-speed communication ensures swift data transfer, enabling real-time monitoring and control.
Elevate your industrial automation capabilities with the Delta DVP04TC-E2 4 Point Thermocouple Module. Ensure precision, reliability, and seamless integration for your temperature monitoring needs.
For more information or to integrate this module into your system, contact us today.
Delta DVP04TC-E2 4 Point of Thermocouple (K/J/R/S/T/E/N), 16bit (0.1ЃЋ), 24V DC Power, PID contol
DVP04TC-E2 temperature measurement module receives 4 points of external thermocouple temperature sensors (J-type, K-type, R-type, S-type, T-type, E-type, N-type, +-80mV) and convert them into 16-bit digital signals. Users can select temperatures in Celsius (resolution: 0.1°C) or Fahrenheit (resolution: 0.1°F). In addition, you can access the data in the module by applying FROM/TO instructions or read the average value of channels directly by using MOV instruction (Please refer to allocation of special registers D9900 ~ D9999).
Electrical Specifications
DVP04TC-E2 | |
Power supply voltage | 24VDC (20.4VDC ~ 28.8VDC) (-15% ~ +20%) |
Max. rated power consumption | 1.2W, supplied by external power source |
Connector | European standard removable terminal block (Pin pitch: 5mm) |
Operation/storage | Operation: 0°C~55°C (temp.), 5~95% (humidity), Pollution degree2 Storage: -25°C~70°C (temp.), 5~95% (humidity) |
Vibration/shock immunity | International standards: IEC61131-2, IEC 68-2-6 (TEST Fc)/ IEC61131-2 & IEC 68-2-27 (TEST Ea) |